Motor Full-Load Current Calculator

Estimate FLA from HP, efficiency and PF, cross-checked against the NEC Table 430.250 dataset. 4 inputs, 5 outputs with grouped results.

Inputs

Nameplate

Standard HP from NEC Table 430.250; table FLA is looked up exactly.

Line-to-line volts.

Performance

Nameplate efficiency.

Typical 0.8-0.9 at full load.

Result

Estimate vs table
-1.8 A
Estimated full-load current
12.2 A
NEC 430.250 table FLA
14.0 A
Input kVA
9.75 kVA
Shaft power
7.46 kW
Screening calculation only. Verify against NEC articles cited on the page and the equipment nameplate; the authority having jurisdiction governs.

Related calculators

Calculator

Motor Branch Circuit Sizer

Gauge-picked conductor at 125% FLA, ground reference, conduit fill hint and voltage at motor. 6 inputs, 4 outputs with grouped results.

Outputs: Min conductor ampacity · Chosen gauge adequate (1=yes) · Drop at motor

Open calculator

Calculator

Motor Overload Setting Calculator

Overload pickup at 115/125% FLA per NEC 430.32 with service-factor and temperature-rise selection. 4 inputs, 3 outputs with grouped results.

Outputs: Overload pickup · Setting band low · Setting band high

Open calculator

Calculator

Multi-Motor Load Summary

Feeder for up to five motors: 125% largest + rest per NEC 430.24, plus other load, standard main. 8 inputs, 5 outputs with grouped...

Outputs: Motor total · Feeder ampacity · Feeder kVA

Open calculator

Calculator

Overcurrent Protection Sizer

Continuous vs noncontinuous, motor inrush reference, standard NEC 240.6 size via dataset ceiling lookup. 4 inputs, 4 outputs with grouped results.

Outputs: Sized load · Standard OCPD size · Motor branch calc

Open calculator

Workspace

Keep the assumptions with the result.

Save this calculation to return to the inputs, result, and report from your private workspace.

Sign in or create an account to save this calculation.